Tel: +86-533-3818450
   Fax: +86-533-3818724
   Email: sales@yuanxing.net

 

 

 

 

 
Split Core Current Transformers \ 0.333V Rated Secondary Output
 Features
   ●   Low cost
   ●   split core design,safer,easier installation, portable
 Applications
   ●   Measures AC current flow to electric motors,
         lighting,air condition equipment,etc. Compatible
         with HVAC temperature control,power manage-
         ment,building automation systems.
 Specifications
   ●   Rated output:0.333Vac
   ●   Accuracy:±1% from 10% to 130% of rated current
   ●   Phase Angle:less than 2 degrees at 50% of rated
         current
   ●   Insulation Voltage:600Vac
   ●   Maximum Primary Voltage:5000Vac(Insulated
         Conductor)
   ●   Operating Temperature:-15℃to 60℃.
   ●   Case Material:ABS Resin UL flame retardant
         rating 94V-O
   ●   Frequency Range:50/60Hz
   ●   Leads:5Foot(1.5m),UL 1015,Twisted Pair,
         0.34 mm2(22AWG)
   ●   UL&CE recognized.
Typical Products
Photograph Part
Number
Rated
Input/output
Frequency
(Hz)
Accuracy
Class
Outline
Dimensions
(mm)
pdf
CTS0191  Input:5,10,30,50,75,100,150,
         200A
 Output:0.333V
50 to 400 1.0 L-W-H
50.8-53.3-17.0
CTS0318  Input:75,100,150,200,300,400,
         600A
 Output:0.333V
50 to 400 1.0 L-W-H
82.5-85.1-27.0
CTS0508  Input:100,200,300,600,800,1000,
         1500A
 Output:0.333V
50 to 400 1.0 L-W-H
121.0-127.0-30.0
CTS0712  Input:600,800,1000,1500,2000,2500,
         3000A
 Output:0.333V
50 to 400 1.0 L-W-H
190-145-27.6